Tag Archives: Power System

Basics and Setting of Parameters for Protection of Transmission Line

Transmission Line is one of the major components of electrical power system; commonly it can be related with highway of electrical energy from where energy is transferred from source to load. Since, overhead transmission line are directly exposed with outer atmosphere and it passes through different land profile with varying climate, protection of transmission line is one of the major concern for power system operators.  The failure of transmission line may lead to system instability ultimately resulting in system collapse, which is often seen and observed as headache for operators. In this blog, I will be discussing about the basics of transmission line protection and relay setting parameters required for protection of transmission line.

The protection of transmission line is broadly classified in two categories which are further classified according to protection requirements required by utility considering the sensitivity of transmission lines:

1) Main Protection

The main protection of transmission line is achieved by distance protection generally referred as 21 in device numbering. Distance relaying are considered since overcurrent relaying is too slow or is not selective. Distance relays are preferred to overcurrent reIays because they are not nearly so much affected by changes in short-circuit-current magnitude as overcurrent relays are, and, hence, are much less affected by changes in generating capacity and in system configuration.

2) Backup Protection

Directional overcurrent and earth fault are generally referred as backup protection referred as 67/67N in device numbering.

The protection of transmission line is done at substation where the particular lines are terminating. We have read lot about theory in books thus I am jumping directly towards the content starting with figure given below:

Figure 1 represents the single line diagram adopted for transmission line protection at double bus substation where LINE 1 is terminated. The protection associated with LINE 1 shall be employed at substation represented with double bus in given figure. Since we are only concerned with protection of transmission line, only short introduction regarding other protection shown in single line diagram will be given.

Fig 1 SLD

Figure 1: SLD of transmission line protection

It is very well known to us that input to relay for desired protection is given by CT which generally serves two purposes: metering and protection. Here, metering core is designated as core 2 with accuracy class of 0.2. Core 1, Core 3, Core 4 and Core 5 serves the purpose for protection where Core 1 is used as main protection, i.e. distance protection (21) whereas Core 3 serves for backup protection and Core 5 is employed as busbar differential protection. It’s better to employ PS accuracy class CT for protection since there are no issues regarding CT saturation.

According to basic protection philosophy, core towards bus shall be used for line protection and core towards line shall be used for bus protection to cover the entire protection zone between CT cores.

Setting Parameters for Main Protection (Distance Relay, 21)

  1. General Parameters

Before getting started with setting parameters, first of all required data needs to be gathered and accessed, calculated and then finally to be written in relay for proper functioning of desired protection. Figure 2 represents the general information regarding parameters at Substation A. The line considered in this blog is of 132 kV voltage level, however voltage level does not affects the setting procedures. Process is same for 220 kV, 400 kV, 765 kV and 1200 kV lines.

Figure 2 General

Figure 2: General Information of Parameters

The only complicated thing to be calculated is positive and zero sequence impedance of line which is major input for operation of distance relay. The properties of conductor, OPGW/earth wire and tower configuration is required for computation of sequence impedances. It can be calculated manually or with the help of software like MATLAB, Power World Simulator etc. or with impedance measurement equipment. Generally, I prefer to use Simulink of MATLAB with tool ‘Compute RLC line parameters’ for computation of sequence impedance. The graphical interpretation of protected line and adjoining line are shown in Figure 3.

Figure 3 GRaphical Line

Figure 3: Graphical Interpretation of protected line

 

2) Parameters for Line Protection

After done with the general parameters we need to calculate the positive sequence, zero sequence and mutual impedance of overall line length of protected line and every adjoining lines which has been shown in figure 4. Since, we are concerned with protection of single circuit line there is no zero sequence mutual impedance, only positive and zero sequence impedance are presented.

Figure 4 protected line

Figure 4: Parameters for protected line

Similarly, the parameters for line in reverse from local end and adjoining line from remote end are calculated in same way which has been given in figure 5.

Figure 5 adjoiining line

Figure 5: Parameters for adjoining lines

 3) Zone Reach Settings

The features of distance relay is that line is protected by dividing the line into different zones considering its length as well as length of adjoining lines from local and remote end. Generally, distance relay functions by separating into five (5) zones referred as zone 1, zone 2, zone 3, zone 4 and zone 5. The zone 4 and zone 5 are known as reverse zone whereas former three zones operate in forward region. The zone reach setting may vary according to grid code or standards of utility or country, but here I will be showing general setting criteria for respective zones as given below:

Zone 1:            80-85 % of protected line

Zone 2:            120 % of protected line

Zone 3:            120 % of protected line + 120 % of longest line from remote end

Zone 4:            20% of protected length

Zone 5:            not required here

The zone reach setting for distance relay alongwith operating time for respective zones has been shown in figure 6. The operating time may be adjusted as according to requirements or standards set by regulator/utility/country.

Figure 6 reach setting

Figure 6: Zone Reach Setting for Distance Relay

After calculating the zone reach setting, you need to input this data into relay in their format which may be different for every manufacturer like ABB, GE, Alstom, CG etc. because parameter name adopted by manufacturer is different, however the procedure is same. For that you need to read the relay manual and input this data as described.

Setting Parameters for Backup Protection

  1. Directional O/C and E/F, 67/67N

Before getting started with settings for directional overcurrent and earth fault relay, let us review the operating time of different categories of IDMT relay. Generally there are three types of IDMT relay having Standard (Normally) Inverse, Extremely Inverse and Very Inverse characteristics which have different operating time.

Figure 6 IDMT

Figure 7: IDMT Relay characteristics

Since, we are using normally inverse relay for this purpose, we have adopted this relay characteristics for calculation of operating time.

Figure 8 backup

Figure 8: 67, 67N Setting Parameters

Base Current means the tapped CT ratio at primary whereas full load current means the maximum load current expected to be carried by line. The pick-up setting for overcurrent is generally set as 110% or 120% whereas for earth fault it is set as 10% or 20% of full load current.

2) Breaker Failure Protection (50BF)

Pick – up set same as earth fault protection, i.e, 0.15 x In. The breaker failure protection is set with 2 stages, one for re-trip and the other back- up trip.

The time delay is adopted based on the calculation below.

Re – Trip Time Delay (minimum) = Relay Reset Delay + CB Opening Time Delay + Margin

= 20 + 40 + 20

= 80 ms

Re – Trip Time Delay (Set)     = 100 ms

Back- Up – Trip Time Delay

(minimum)                          =  Re – Trip Time Delay + Relay Reset Delay + CB   Opening

Time Delay + Margin

= 100 + 15 + 40 + 20

= 175 ms

Back – Up – Trip Delay (Set) = 200 ms

Beside this, there are various other auxiliary protection features provided by manufacturer for line protection such as broken conductor detection, power swings, fault locator etc. the setting of which are also derived from the parameters calculated above.

Hope you have enjoyed this blog. If there are any queries regarding the content of the blog, please feel free to write me at

            -Anand Mandal (anandkalyaneee@gmail.com)

1 Comment

Filed under Uncategorized

FACTS and HVDC

SIMILARITY BETWEEN FACTS AND HVDC

While some of the relevant technology i.e., Static VAR Compensation is already in wide use, the FACTS concept has brought to the table a tremendous potential for thyristor based controllers which will surely revolutionize the power system. The technology offers the utilities the ability to:

1. Control power flows on their transmission routes;
2. Allow secure loading of transmission lines to their full thermal capacity.

FACTS technology, while allowing use of transmission to its thermal capacity, does not do away with the need for additional transmission lines or the upgrading of existing lines where thermal limits have been reached or when evaluation of losses added to the cost of FACTS technology shows that new lines or upgrading of existing lines is the most optimum answer.

Often, ac transmission systems are thought of as being “inflexible”. Power flow in ac networks simply follows Ohm’s law and ordinarily cannot be made to flow along specific desired paths. As a result, ac networks suffer from parallel-path, or “loop” flows. The power flows from source to load in inverse proportion to the relative impedances of the transmission paths. Low  impedance paths take the largest fraction of flow, but all lines in the interconnection are a part of the flow path. Thus, utilities not involved in an interchange power transaction can be affected.

A fundamental notion behind FACTS is that it is possible to continuously vary the apparent impedance of specific transmission lines so as to force power to flow along a “contract path”. This is a brand-new concept for many system planners. As illustrated in Figure 1, with precise control of the impedance of transmission lines using FACTS devices, it is possible to maintain constant power flow along a desired path in the presence of continuous changes of load levels in the external ac network, and to react in a planned way to contingencies. Just as in HVDC applications, FACTS controls could be designed to enhance the behavior of the uncontrolled systems.

UntitledFig. 1: FACTS can direct flow along a desired path

The flexible system owes its tighter transmission control to its ability to manage the interrelated parameters that constrain today’s systems ,including series impedance, shunt impedance, phase angle, and the occurrence of oscillations at various frequencies below the rated frequency. By adding to in this way, the controllers enable a transmission line to function nearer its thermal rating. For example, a 500-kV line may have a loading limit of 1000-2000 MW for safe operation, but a thermal limit of 3000 MW.

It is often not possible both to overcome these constraints and maintain the required system reliability by conventional mechanical means alone, such as tap changers, phase shifters, and switched capacitors and reactors (inductors). Granted, mechanical controllers are on the whole  less expensive, but they increasingly need to be supplemented by rapidly responding power electronics controllers.

The new technology is not a single, high-power electronic controller, but rather a collection of controllers, which can be applied individually or collectively in a specific power system to control the five interrelated functions already mentioned. The thyristor is their basic element, just as the transistor is the basic element for a whole variety of microelectronic circuit. Because all controllers for the flexible transmission system are applications of similar technology, their use will eventually benefit from volume production and further development of high-power electronics.

Electric power networks integrate generation and load centers within each utility system and through interconnections among neighboring systems, share power with vast regional grids. The purpose of this is to take advantage of the diversity of loads, changes in peak demand due to weather and time differences, the availability of different generation reserves in various geographic regions, power sharing arrangements among utilities , shifts in fuel prices, regulatory changes, and other discrepancies.

 

Applying Flexibility to the Electric Power System

The power industry term FACTS (Flexible AC Transmission Systems) covers a number of technologies that enhance the security, capacity and flexibility of power transmission systems. FACTS solutions enable power grid owners to increase existing transmission network capacity while maintaining or improving the operating margins necessary for grid stability. As a result, more power can reach consumers with a minimum impact on the environment, after substantially shorter project implementation times, and at lower investment costs – all compared to the alternative of building new transmission lines or power generation facilities.

The two main reasons for incorporating FACTS devices in electric power systems are:
· Raising dynamic stability limits

· Provide better power flow control

Benefits of FACTS

Rapidly Implemented Installations: FACTS projects are installed at existing substations and avoid the taking of public or private lands. They can be completed in less than 12 to 18 months—a substantially shorter timeframe than the process required for constructing new transmission lines.

Increased System Capacity: FACTS provide increased capacity on the existing electrical transmission system infrastructure by allowing maximum operational efficiency of existing transmission lines and other equipment.

Enhanced System Reliability: FACTS strengthen the operational integrity of transmission networks, allowing greater voltage stability and power flow control, which leads to enhanced system reliability and security.

Improved System Controllability: FACTS allow improved system controllability by building “intelligence” into the transmission network via the ability to instantaneously respond to system disturbances and gridlock constraints and to enable redirection of power flows.

Seamless System Interconnections: FACTS, in the form of BTB dc-link configurations, can establish “seamless” interconnections within and between regional and local networks, allowing controlled power transfer and an increase in grid stability.

 

ANAND MANDAL

E-mail: anandkalyaneee@gmail.com

 

1 Comment

Filed under Uncategorized